Delta DVP16SM11N
Model Item |
08SM11N 08SM10N
|
DVP16SM11N |
08SN11R/T |
08SP11R/T |
16SP11R/T |
DVP16SP11TS
|
06SN11R |
Power supply voltage |
24VDC (-15%~20%)(with DC input polarity reverse protection) |
||||||
Motion specification |
Within 5ms of the momentary power loss, the device will keep on operating |
||||||
Power consumption |
1W |
2W |
1.5W |
1.5W |
2W |
2W |
1.5W |
Insulation resistance |
>5m ohm (all I/O) point-to-ground: 500VDC) |
||||||
Noise immunity |
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge EFT: (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 1KV Damped-Oscilatory Wave: Power Line: 1KV, Digital I/O:1KV RS (IEC 61131-2, IEC 61000-4-3): 26MHz~1GHz, 10V/m |
||||||
Grounding |
The diameter of grounding wire shall not be less than that of L,N terminal of the power supply. (When many PLCs are in use at the same time, please make sure every PLC properly grounded.) |
||||||
Operation/storage |
Operation: 00C~550C(temperature), 50~95%(humidity), pollution degree 2 Storage: -250C~700C (temperature), 5~95%(humidity) |
||||||
Vibration/shock /immunity |
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) |
||||||
Weight(g) |
162/141 |
146 |
154/146 |
141/136 |
162/154 |
151 |
200 |