Receptor bus X20BR9300 X2X B&R

  • Receptor de bus de enlace X2X
  • Alimentación para X2X Link y fuente de E/S interna
  • El aislamiento eléctrico de la alimentación y el suministro X2X Link
  • La redundancia de la conexión X2X Link es posible operando múltiples módulos de suministro simultáneamente
  • Operación sólo en la ranura a la izquierda
Short description X20BR9300
Bus receivers X2X Link bus receiver with supply for I/O and bus
General information X20BR9300
B&R ID code 0x1BC1
Status indicators X2X bus function, overload, operating status, module status
Diagnostics  
Module run/error Yes, with status LED and software status
Overload Yes, with status LED and software status
X2X bus function Yes, with status LED
Power consumption 1)  
Bus 1.62 W
Internal I/O 0.6 W
Additional power dissipation caused by the actuators (resistive) [W] -
Electrical isolation  
I/O feed - I/O supply No
X2X Link feed - X2X Link supply Yes
Certification types  
CE Yes
c-UL-us Yes
GOST-R Yes
X2X Link supply input X20BR9300
Input voltage 24 VDC -15% / +20%
Input current Max. 0.7 A
Fuse Integrated, cannot be replaced
Reverse polarity protection Yes
X2X Link supply output X20BR9300
Rated output power 7.0 W
Parallel operation Yes 2)
Redundant operation Yes
Overload behavior Short circuit / temporary overload protection
Input I/O supply X20BR9300
Input voltage 24 VDC -15% / +20%
Fuse Erforderliche Vorsicherung max. T 10 A
Reverse polarity protection No
Output I/O supply X20BR9300
Rated output voltage 24 VDC
Behavior if a short circuit occurs Erforderliche Vorsicherung
Permitted contact load 10.0 A
Operating conditions X20BR9300
Mounting orientation  
Horizontal Yes
Vertical Yes
Installation at altitudes above sea level  
0 to 2000 m No limitations
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection IP20
Environmental conditions X20BR9300
Temperature  
Operation  
Horizontal installation -25°C to +60°C
Vertical installation -25°C to +50°C
Derating When operated at temperatures above 55°C, the rated output current for the X2X Link supply is reduced to 5 W.
Storage -40°C to +85°C
Transport -40°C to +85°C
Relative humidity  
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical characteristics X20BR9300
Note Order 1x X20TB12 terminal block separately
Order 1x X20BM01 supply module separately
Left and right X20 end plates included in delivery
Spacing 12.5+0.2 mm
   
1) The values specified are maximum values. The exact calculation is also available for download as a data sheet with the other module documentation on the B&R homepage.
2) In parallel operation, only 75% of the rated power can be assumed. Please ensure that all parallel operating power supplies are switched on and off simultaneously.